NeXTimber engineering product catalogue
v3.0

Fire Performance Guide

How NeXTimber CLT and GLT perform in fire: melamine glue-line integrity, notional and calculated char rates, fire resistance levels, and the encapsulation and joint detailing needed to achieve an FRL.

Request a spec

Product overview and adhesive performance

NeXTimber CLT and GLT are made from responsibly sourced Australian plantation radiata pine, bonded with Melamine Formaldehyde (MF) adhesive cured under pressure. Melamine is a thermoset polymer with high hydrolysis resistance that maintains thermal stability past the combustion point of the timber fibres.

Warringtonfire testing demonstrates that NeXTimber products maintain glue-line integrity in fire and char at a constant linear rate, giving predictable, reliable fire performance comparable to solid timber. Unlike some polyurethane adhesives, the melamine glue line does not delaminate or cause char fall-off. A fire-exposed section develops three zones: an unburnt timber core, a pyrolysis layer, and a partially charred layer, with a residual cross-section that can be analysed for structural adequacy.

Fire testing and reports

Testing was carried out by Warringtonfire in accordance with AS 1530.4, with assessment by Jensen Hughes. The results are summarised in a Regulatory Information Report (RIR), available on request. Seven fire test reports (FRT series), one assessment (FAS210228) and the RIR underpin the ratings below.

Products used in assessment
ProductDescription
NeXTimber CLT and GLTRadiata pine
AdhesiveMelamine formaldehyde
Fire rated sealantBostik Fireban acrylic
Fire-grade plasterboard16 mm Boral / Knauf fire-grade
AS 1530.4 (fire tests)AS 1720.1 (timber structures)AS/NZS 1720.4 (fire resistance)NCC 2022 Vol One Spec 7

Fire resistance levels (FRL / FRR)

A Fire Resistance Level (FRL), used interchangeably with Fire Resistance Rating (FRR), is expressed as three numbers, for example 90/90/90, meaning the element sustains each of the following for 90 minutes under AS 1530.4:

  • Structural adequacy - maintains strength and serviceability for the FRL period.
  • Integrity - prevents the passage of flames, smoke or hot gases through the surface or joints.
  • Insulation - keeps the average temperature rise on the non-fire side below 140 degrees C, with a peak rise below 180 degrees C.

Being a natural timber product, NeXTimber CLT and GLT cannot be modified to meet a non-combustible building element requirement. Where higher performance is required, add fire-grade plasterboard or non-combustible linings. In Australia, intumescent coatings are not recognised under DTS provisions and require a performance solution developed by the fire engineer.

Fire hazard and lining properties (Radiata pine)
PropertyValue
Spread of Flame Index (0-10)8
Smoke-Developed Index (0-10)3
Critical Radiant Flux (kW/m2)Greater than 2.2 and less than 4.5
Smoke Development Rate (% mins)Less than 750
Material group numberGroup 3 (avg extinction area under 250 m2/kg)

CLT char rates and residual sections

Char rates and depths for NeXTimber CLT were determined by test and assessment by Warringtonfire. The effective depth of charring after time t is calculated as dc = sum(c x delta-t) + 7 mm, where c is the notional charring rate for the interval and the 7 mm accounts for a zero-strength layer of heated but uncharred timber. The residual section should then be assessed by the structural engineer, subtracting both the char depth and the zero-strength layer. Below splines and lap joints the calculated char depth must maintain a minimum 20 mm of cover: t.min = sum(c x delta-t) + 20 mm.

Notional char rates - CLT
SystemTime period (mins)Char rate (mm/min)
Unprotected floors and walls0 - 1200.80
Protected with 1 layer 16 mm fire-grade plasterboard0 - 300.00
Protected with 1 layer 16 mm fire-grade plasterboard30 - 1200.35
Protected with 1 layer 16 mm fire-grade plasterboard120 - 1800.80
Integrity and insulation - minimum initial panel thickness (mm)
Time (mins)Wall half-lap, unprotectedWall half-lap, encapsulatedFloor half-lap, unprotectedFloor 35 mm spline, unprotectedFloor half-lap or spline, encapsulated
309090909090
6090909011090
901809018013090
120230100230150100
180-200--200
The FRL is only valid if the structural engineer confirms structural adequacy. Spline plate connections are not permitted on the fire side of wall-to-wall connections. Encapsulated indicates one layer of 16 mm fire-grade plasterboard fixed per the test report.

GLT char rates and residual sections

Predicted effective char depths for NeXTimber GLT are shown below, including the 7 mm zero-strength layer defined in AS/NZS 1720.4. The residual structural capacity is determined using AS 1720.1 with actions from AS/NZS 1170.0. Refer to the NeXTimber Technical Guide for standard GLT section sizes.

Predicted effective char depth - GLT
Time (mins)GLT only (mm)GLT + 1 layer 16 mm FRPB (mm)GLT + 2 layers 16 mm FRPB (mm)
3031.07.07.0
6055.022.07.0
9079.046.07.0
120103.070.031.0
Char depths include the 7 mm zero-strength layer as defined in AS/NZS 1720.4.

Encapsulation, joints and design considerations

Wrapping timber elements in fire-grade plasterboard (FRPB) slows the charring rate. The FRPB screw pattern and screw length are essential to achieving the FRL, so follow the encapsulation fixing details in the guide. Panels must be tightly fitted, screwed together and caulked inside the joint to maintain integrity and insulation. Floor joints can use a lap or spline joint; spline plate connections are not permitted in wall-to-wall connections where an FRL is required.

Interfaces with other materials are generally protected with intumescent strips, mineral wool or fire-rated caulking. Floor and wall penetrations require specific tested systems. For connections, encase fixings in timber by overdriving and plugging, provide sufficient encapsulation to internal plates, add passive fire protection, and provide redundancy. Refer to AS/NZS 1720.4 for additional guidance and obtain specialist advice.

Fire-grade plasterboard fixing (typical)
ItemSpecification
CLT wall fixings65 x 8g W screws
CLT ceiling fixings75 x 8g W screws
GLT, 1 layer FRPB6-9g 40 mm screws
GLT, 2 layers FRPB6-9g 60 mm screws
Screw grid / edge200 mm max grid, 20 mm nominal from edge