Wall Footing (ACI 318-14)

Run the calc
Footing loads link to the wall above, so load changes propagate downstream automatically. Design continuous wall footings to ACI 318-14. Results cover ultimate load, bearing capacity, and serviceability.
This calculator uses an earlier code edition (ACI 318-14). It stays available for existing projects. For new designs, check the Calculator Library for the current edition.

Method & scope

Calculation method

The Wall Footing (ACI 318-14) calculator designs continuous strip footings per ACI 318-14 (IBC 2018), using ASCE 7-16 load combinations. It checks bearing pressure under service loads, flexural reinforcement demand, one-way shear, and development length adequacy.
Bearing pressure check (ASD, ASCE 7-16, Ch. 2)
Service loads are combined using ASD load combinations to compute the gross soil bearing stress q_s across the footing width: utilization = q_s / q_a ≤ 1.0 Stability checks for sliding (FS_s) and overturning (FS_ovt) are also reported. The calculator confirms the footing remains in total compression (resultant within the kern) under service loads.
Flexural design (ACI 318-14, Cl. 22.2)
Factored moment demand M_u is taken at the critical section (face of the wall) from the net upward bearing pressure under LRFD load combinations. Required reinforcement area is determined and compared to the provided area and minimum steel: A_s,min = 0.002 × H × b (temperature and shrinkage reinforcement governs for most plain wall footings) utilization = M_u / (phi × M_n) ≤ 1.0
One-way shear (ACI 318-14, Cl. 22.5)
The critical shear section is at distance d from the wall face. Plain concrete shear strength: phi × V_n = phi × 2 × lambda × sqrt(f’c) × b × d utilization = V_u / (phi × V_n) ≤ 1.0 No shear reinforcement is included. If shear demand exceeds capacity, the calculator checks whether a plain concrete design will satisfy the requirements.
Development length (ACI 318-14, Cl. 25.4)
Available development distance l_a = B/2, b/2, cover. Required development length l_d is calculated per ACI 318-14 and reduced for excess reinforcement area. If insufficient, the calculator automatically checks whether a plain concrete design passes.
Top reinforcement for negative bending
Where overturning moments generate tension at the top of the footing, top bar reinforcement is checked for negative bending capacity and development length per ACI 318-14 Cl. 22.2 and 25.4.
Assumptions
Wall is centered on the footing. Lateral loads are only used for sliding checks. No shear reinforcement is considered. Compression reinforcement is not included in bending calculations. Wall reinforcement is assumed to continue into the footing without splice checks at the interface.

How to use it

1

Open the calculator

Open it from Run calc in the About this calculator panel above.
2

Enter your inputs

Work through the input sections from top to bottom. Click any input label to see its reference explanation, clause, conditions and assumptions. See Checks, References, Conditions and Assumptions.
3

Review the results and export

Check the utilization of each governing check in the summary, then export a PDF report. See Views and Export.

Common questions

The calculator applies ACI 318-14 for reinforced concrete section design per IBC 2018 load combinations (ASCE 7-16). Strength design (LRFD) is used, factored loads are checked against reduced design capacities (phiMn, phiVn). Bearing pressure is checked against allowable capacity under service loads.
Key inputs are wall thickness, footing width and depth, concrete compressive strength (f’c), reinforcement bar size and spacing, concrete cover, allowable soil bearing pressure (qa), and applied loads per unit length of wall (axial force, overturning moment, shear). Loads can be entered directly or linked from a wall calculation above.
Checks include: bearing pressure under service loads versus allowable bearing capacity, ultimate flexural demand at the face of the wall versus design moment capacity (phiMn), one-way shear at d from the wall face versus shear capacity (phiVc), and minimum reinforcement per ACI 318-14. Required and provided reinforcement areas and utilization ratios are reported.
Use this ACI 318-14 calculator for projects governed by IBC 2018 or when the authority having jurisdiction requires the 2014 edition. For projects under IBC 2021 or newer, use the Wall Footing (ACI 318-19) calculator instead, which incorporates the updated shear design provisions including the size effect factor introduced in ACI 318-19.
Yes. All footing checks update automatically when the wall above changes. For foundation design where wall loads drive footing sizing, linking the reactions from the wall calculation keeps the footing design current through the full load path without manual re-entry.

Next steps

Calculator Library

Complete list of Calcs.com design calculators available for United States projects (AISC, ACI, NDS, ASCE 7, IBC, and related standards).

Design a Wall Footing to ACI 318-19

Design continuous wall footings to ACI 318-19 per IBC 2021 or IBC 2024. Results cover ultimate load, bearing capacity and serviceability.

Design a Pier Footing to ACI 318-14

Design pier and deck footings to ACI 318-14 (IBC 2018). An earlier code edition, kept for existing projects.

Design a Cantilever Retaining Wall (IBC 2021)

Design concrete or CMU cantilever retaining walls to IBC 2021, ASCE 7-16, ACI 318-19 and TMS 402-16. An earlier edition, kept for existing projects.

Design a Restrained (Basement) Retaining Wall (IBC 2021)

Design restrained (basement) retaining walls to IBC 2021, ASCE 7-16 and ACI 318-19. An earlier code edition, kept for existing projects.