This article will discuss the input parameters in the Distributed Loads table and gives some worked examples on how to input distributed loads into Calcs.com for structural design applications.
Input Parameters
| Parameter | Description |
|---|---|
| Start Location (A) | The distance from the left end (zero point) of the beam where the load begins. Measured in millimetres. |
| End Location (B) | The point where the load ceases to act, measured from the left end (zero point) of the beam. Measured in millimetres. Use βLβ for the right end of the beam. |
| Tributary Width (C & D) | The width of the area from which the member obtains its load. See the explanation below for details. |
| Load Magnitude (E) | The pressure magnitude, entered in kilopascals (kPa). Click the cell to open a table where you can select the load type and enter the value. |
Understanding Tributary Width
Every structural element has an area from which it obtains its load. As with any other area, this can also be expressed as a product of length and width. The length of this area is usually either the length of the element itself or the length of the distributed load (B-A from the table). Tributary width is simply the width of this area. To better illustrate this concept, consider a floor that is supported by members spaced βsβ mm apart.
Key Concept: For most cases, the tributary width is the same as member spacing.
- The starting and ending tributary widths will be different
- Youβll need to enter different values for Total Start Tributary Width and Total End Tributary Width
Load Magnitudes
When you click on the Load Magnitudes cell, a new table will appear (see below).
- First Column: A drop-down menu from which you can choose your load type.
- Second Column: You can input the magnitude of the load in kilopascals (kPa).
Examples
Example 1
Task
Input a live load of 1.5kPa on a floor joist with a member spacing of 450mm.Method
1
Set the Range
Enter 0 for Start Location and L for End Location to apply the load to the full beam.
2
Define Tributary Width
Input the member spacing (450mm) into both the Start and End Tributary Width cells.
3
Apply Load Magnitude
Click the Load Magnitudes cell, select Live Load from the dropdown, and enter 1.5 in the magnitude field.
Example 2
Task
Input a dead load of 0.12kPa on a ceiling joist with a member spacing of 600mm.Method
1
Set the Range
Enter 0 for Start Location and L for End Location to apply the load to the full beam.
2
Define Tributary Width
Input the member spacing (600mm) into both the Start and End Tributary Width cells.
3
Apply Load Magnitude
Click the Load Magnitudes cell, select Dead Load from the dropdown, and enter 0.12 in the magnitude field.
Example 3
Task
Input a live load of 0.25kPa and a dead load of 0.9kPa on a rafter with 600mm member spacing.Method
1
Set the Range
Enter 0 for Start Location and L for End Location to apply the load to the full beam.
2
Define Tributary Width
Input the member spacing (600mm) into both the Start and End Tributary Width cells.
3
Apply Multiple Load Magnitudes
Click the Load Magnitudes cell to open the load table. Add two rows:
- Select Live Load and enter 0.25 in the magnitude field
- Select Dead Load and enter 0.9 in the magnitude field
