What it calculates
Base plate design receives column loads directly from the column calculation, so a load change flows straight to the plate and anchor checks. Designs steel column base plates and anchor rods to ACI 318-19 and AISC 360-22 per AISC Design Guide 1, 3rd Edition, with LRFD bearing, plate bending and thickness, weld, and anchor limit state checks.
Who uses this calculator
US structural engineers designing steel column base plates and anchor rods to ACI 318-19 and AISC 360-22 under LRFD. It uses AISC Design Guide 1, 3rd Edition. Link it to the column calculation above and the column loads come across automatically. The plate thickness defaults to the required minimum, so it resizes with the load until you enter your own.
How it calculates
The Steel Base Plate (LRFD) calculator follows AISC Design Guide 1, 3rd Edition (2024) for plate sizing and bending. Anchor rods in concrete follow ACI 318-19 Chapter 17. AISC 360-22 covers bearing, welds and combined rod tension and shear. Load combinations come from the building code set in your project defaults.
Load combinations
Unfactored dead, live, roof live, snow, rain, wind and earthquake loads are combined into LRFD strength combinations. Concrete bearing and friction use the largest factored compression. Anchor tension is calculated for every combination in each axis, and the largest tension governs.
Plate bending at the bearing interface is also worked out for every combination, using its own axial load and moment. About each axis, the combination that needs the thickest plate governs. Combinations with net uplift are designed for, with the anchors taking the tension. Where net uplift comes with a large enough moment, the plate still bears on one side, and that bearing interface is checked too.
Concrete bearing capacity (ACI 318-19 Cl 22.8, AISC 360-22 Cl J8)
The factored concrete bearing strength, with phi_c = 0.65:
phi × P_p = phi_c × 0.85 × f'c × A_1 × min(sqrt(A_2/A_1), 2)
A_2 is derived from the plate footprint and the concrete base depth, capped at the concrete base footprint. Where grout is considered, the lesser of the grout strength (no confinement increase) and the concrete strength governs.
Utilization = P_u / phi × P_p ≤ 1.0
Plate bending (AISC DG1 Cl 3.3)
The plate is checked at the bearing interface and the tension interface, about each axis. Each axis uses the small-moment (full bearing) or large-moment (anchor tension) approach, and the pure-moment procedure when there is no axial load.
At the bearing interface, the plate bends in both directions, and the larger demand per unit width governs. For moment about the x-axis, with bearing pressure f_p and bearing length Y:
- m bending line, over the full plate width: f_p × m^2 / 2. Where Y < m, it is f_p × Y × (m - Y/2)
- n bending line: f_p × Y × n^2 / 2, over an effective width b_eff. Where Y < 2n, b_eff = Y/2 + n, otherwise b_eff = Y
For moment about the y-axis, m and n swap roles. The two-way bending of the n line follows AISC Design Guide 1 Appendix B.4. Where there is no bearing length, the bearing stress and the bearing interface demand are zero. At the tension interface, the anchor tension acts on the plate over its lever arm to the bending line.
phi × M_n = 0.9 × F_y × t_p^2 / 4
Utilization = M_u,pl / phi × M_n ≤ 1.0
Biaxial bending (beta)
When moment acts about both axes, the connection is checked with the AISC Design Guide 1 biaxial interaction:
Interaction = (M_ux / M_cx)^2 + (M_uy / M_cy)^2 ≤ 1.0
M_cx and M_cy are the connection moment strengths about each axis at the maximum factored compression. Each is limited by the anchor rod tensile strength, plate yielding at the tension and bearing interfaces, and bearing. The rod strength is the lesser of the AISC 360-22 Cl J3.8 rod steel strength and the ACI 318-19 anchor limit states.
The check runs only when no combination is in net uplift and the shear is zero or carried by friction. Otherwise each axis is checked on its own and a note says so. Shears about both axes are not combined either, except in the column-to-plate weld, and a warning says so. Corner rod tension and concrete breakout from both moments together are not yet checked.
Minimum required plate thickness
The required thickness from bending is t = sqrt(4 × M_u,pl / (phi_b × F_y)), with phi_b = 0.9. The governing t_min is the largest of these requirements, with a 1/8 in floor:
- Pure axial bearing
- Bearing interface and tension interface, about each axis
- One-way bending under net uplift with the load inside the anchor group: about the web and flange for I-shapes, or about the column wall for HSS, round HSS and pipe
- Outset anchor rod bending, for rods outside the column footprint
The plate thickness you enter is checked against t_min. Left at its default, the thickness equals t_min and the check reads 100%.
Anchor rods outside the column footprint
For I-shaped, HSS, round HSS and pipe columns, rods outside the column footprint load the plate locally near the rod. Three checks cover this case:
- Plate bending whenever the rod is in tension, from net uplift or moment: a cantilever from the rod to the nearest section corner, with an effective width of up to 5 in
- Weld strain: the rod tension the column-to-plate weld can take before it is overstrained, based on weld throat and plate thickness
- Weld strength: the rod tension the weld can transfer, using only the weld length local to the rod
For round HSS and pipe, the lever arm runs radially to the tube face. These round-section checks are engineering adaptations, since the design guides do not cover round columns.
Column-to-plate weld (AISC 360-22 Cl J2)
The column is assumed fillet welded to the plate with E70XX electrodes. The factored column tension and the moments, as pull-off forces, are combined with the resultant shear into one weld demand. It is compared with the weld group's available strength. The weld size is checked against the minimum for the parts joined and the maximum for the column element thickness. The plate length and width must each be at least the column depth or width plus twice the weld size, so the weld fits. On rectangular HSS columns, the weld length discounts the rounded corners. On round HSS and pipe, the weld runs the full circumference.
Anchor rod tensile limit states (ACI 318-19 Cl 17.6)
Steel tensile capacity is always checked. The concrete checks run when you include them:
- Steel tensile capacity (Cl 17.6.1): phi × N_sa = 0.75 × A_se,N × f_uta per rod. A_se,N is the effective area of the threaded rod, from the rod diameter and the Unified Coarse threads per inch
- Concrete breakout in tension (Cl 17.6.2): projected area method with eccentricity, edge distance and cracking factors, including group effects. Hooked rods always use the general single-anchor breakout equation
- Pullout (Cl 17.6.3): phi × 8 × A_brg × f'c for headed anchors, with a separate equation for hooked anchors
- Side-face blowout (Cl 17.6.4): single anchor and group, applies when h_ef > 2.5 × c_a1
The rod steel above the concrete is also checked on its own under combined tension and shear, per AISC 360-22 Cl J3.8. It uses 0.75 times the gross rod area and a tensile stress reduced for shear. This check is kept separate from the ACI 318-19 anchor checks.
Utilization = N_u / phi × N_n,g ≤ 1.0
Anchor rod shear limit states (ACI 318-19 Cl 17.7)
Three shear limit states are checked in each principal axis:
- Steel shear capacity (Cl 17.7.1): phi × V_sa = 0.65 × 0.6 × A_se,N × f_uta, reduced by 0.8 where grout is considered
- Concrete pryout (Cl 17.7.3): based on the tensile breakout strength of the group
- Concrete shear breakout (Cl 17.7.2): edge distance, cracking and member thickness factors, for shear toward and parallel to the edge. The lower capacity governs
Which anchor row resists shear breakout depends on rod welding to the plate and on whether you allow shear to redistribute between rows.
Utilization = V_u / phi × V_n,g ≤ 1.0
Pryout and shear breakout run only when the concrete checks are included.
Tension and shear interaction (ACI 318-19 Cl 17.8)
When the anchors carry both tension and shear, the tension utilization and the larger shear utilization are added:
Interaction = N_u / phi × N_n,g + V_u / phi × V_n,g ≤ 1.2
Frictional shear capacity
An optional, separate check compares the larger shear demand to friction at the plate interface. It does not add to anchor shear capacity:
phi × V_f = 0.75 × mu × P_u, limited to the lesser of 0.2 × f'c × A_1 and 800 psi × A_1
The friction coefficient mu is taken as 0.4. Grout strength replaces f'c in the limit where grout is considered.
Seismic provisions
Earthquake loads can be entered and are included in the load combinations. The ACI 318-19 Section 17.10 seismic anchor provisions are not applied. The calculator shows a warning when earthquake loads are present.